PRCD User Attachable Plugs
240V/16A
The Schuko Plug configuration is ideal for existing equipment
without PRCD protection, the male connector can be removed and the
PRCD easily attached to the equipment cord. Conforms to the
IEC PRCD standard. Applications include:
- Pressure Washers
- Drain Snakes
- Floor Cleaners
- Industrial Appliances
|
- Power Tools
- Pumps
- Boat Lifts
- Extension Cords
|
To prevent unmonitored equipment startup, manual reset is
required after PRCD trip and power outage.
PRCD User Attachable Plugs Product Sheet
| Part Number | Features | Config | Listed |
|---|
30100
| - Volts/Amps: 240V/16A
- Accepts 1.5 - 2.5mm2 conductor
- Trip Level: 10 mA max.
|  | |
30200
| - Volts/Amps: 240V/16A
- Accepts 1.5 - 2.5mm2 conductor
- Trip Level: 30 mA max.
|  | |
| Operating Voltage Range | 161-264Vac @ 50/60 Hz
|
| Operating Load Current | In = 16 amps max.
|
| Residual Current Trip Window | l∆n (10mA - 30100) or (30mA - 30200)
|
| D. C. Residual Currents | 0˚- .35 l∆n min, 10mA - 2 l∆n, 30mA - 1.4 l∆n; 90˚- .25 l∆n min, 10mA - 2 l∆n, 30mA - 1.4 l∆n; 135˚- .15 l∆n min, 10mA - 2 l∆n, 30mA - 1.4 l∆n
|
| Response Time | 300mS max at l∆n; 150mS max at 2l∆n; 40mS max at 5l∆n; 40mS max at 250A
|
| Contacts | Normally Open (Manual Reset), Contacts open with loss of power
|
| Contacts Closed Indicator | Red flag
|
| Insulation Resistance | 50 Megohms after 500vdc for 1 min.
|
| Dielectric Strength | 2KV 50/60Hz for 1 min.
|
| Over Current | Operates with 250 amp momentary load
|
| Short Circuit | Contacts open with a 1500 amp shorted Residual, Current ( line conductor to Earth or Neutral)
|
| Reliability | 5000 operations minimum with rated load |