GFCI In-Line Cord Sets
120V/15A
Excellent for industrial plant maintenance, equipment service
and construction site applications. Provides compliance with
National Electric Code (NEC 2008) Article 590.6 for "Temporary
Installations". Applications include:
- High Pressure Sprayer Washers
- Construction Site Power Tools
- Drain Snakes
|
- Pumps
- Construction Sites
- Industrial Appliances
|
Rainproof rated, UL listed for outdoor use. Standard
Lengths: 2', 6', 25', 50' and 100'. Custom cable gauges,
lengths and terminations available by special order. To
prevent unmonitored equipment startup, manual reset is required
after GFCI trip and power outage.
GFCI In-Line Cord Sets Product Sheet
| Grounded neutral | 4 Ohms typical
|
| Trip response time for ground fault and grounded neutral trip | less than 25mS
|
| Voltage surge withstand | 3kv ringwave test and 4kv/2kA surge immunity test
|
| Radio frequency noise susceptibility | operates within normal limits with 0.5 volts injected on power line 150kHz-230mHz
|
| Frequency | 50/60 Hz
|
| Endurance | 3,000 operations minimum
|
| Overload current | six times rated current
|
| Operating temperature range | -35˚C to 66˚C
|
| Effect of 10 Amp turn DC Shock on ground fault trip | 5% maximum trip level variation
|
| Insulation voltage | 1500 VRMS - 1 Min.
|
| Power on indication | lighted indicator |