GFCI Protected
In-line Tri-Cord Sets
120V/15A
Heavy duty molded T-head with three receptacles. Provides
protection for the extra heavy duty cord and three attached
tools. 12 gauge cord is ideal for outdoor - rugged
construction type environments. Applications include:
- Construction Sites
- Saws and Drills
|
- Portable Electric Power Tools
- Multiple Tools Use
|
Standard lengths 2', 25' and 50'. To prevent unmonitored
equipment startup, manual reset is required after GFCI trip and
power outage. Provides compliance with National Electric Code
(NEC 2008) Article 590.6 for "Temporary Installations".
GFCI Protected In-line Tri-Cord Sets Product Sheet
| Grounded neutral | 4 Ohms typical
|
| Trip response time for ground fault and grounded neutral trip | less than 25mS
|
| Voltage surge withstand | 3kv ringwave test and 4kv/2kA surge immunity test
|
| Radio frequency noise susceptibility | operates within normal limits with 0.5 volts injected on power line 150kHz-230mHz
|
| Frequency | 50/60 Hz
|
| Endurance | 3,000 operations minimum
|
| Overload current | six times rated current
|
| Operating temperature range | -35˚C to 66˚C
|
| Effect of 10 Amp turn DC Shock on ground fault trip | 5% maximum trip level variation
|
| Insulation voltage | 1500 VRMS - 1a Min.
|
| Power on indication | lighted indicator |