GFCI Protected
In-Line Quad Boxes
120V/20A
Box enclosed in heavy impact resistant polymer case.
Spring loaded covers protect each pair of receptacles. "Fast
Breaker" built in for convenient reset. GFCI with lighted
indicator located at power end provides protection to the cord and
tools attached. Applications include:
|
|
- Lighting
- Multiple tools
- Construction Sites
|
Standard lengths: 2', 6', and 25'. To prevent unmonitored
equipment startup, manual reset is required after GFCI trip and
power outage. Complies with National Electric Code (NEC 2008)
Article 590.6 for "Temporary Installations".
GFCI Protected In-Line Quad Boxes Product Sheet
| Part Number | Features | Config | Listed |
|---|
25080-121 (2’)
25080-122 (6’)
25080-123 (25’)
| - Volts/Amps: 120V/20A
- Cord Gauge: 12/3 AWG.
- NEMA 5-20P & (4)5-20R Outlets
- Trip Level: 4 - 6 mA
- 20A breaker
|  |   |
| Grounded neutral | 4 Ohms typical
|
| Trip response time for ground fault and grounded neutral trip | less than 25mS
|
| Voltage surge withstand | 3kv ringwave test and 4kv/2kA surge immunity test
|
| Radio frequency noise susceptibility | operates within normal limits with 0.5 volts injected on power line 150kHz-230mHz
|
| Frequency | 50/60 Hz
|
| Endurance | 3,000 operations minimum
|
| Overload current | six times rated current
|
| Operating temperature range | -35˚C to 66˚C
|
| Effect of 10 Amp turn DC Shock on ground fault trip | 5% maximum trip level variation
|
| Insulation voltage | 1500 VRMS - 1a Min.
|
| Power on indication | lighted indicator |