GFCI Protected
Right Angle Plug Quad Boxes
120V/15A
Enclosed in heavy impact resistant polymer case. Spring
loaded covers protect each pair of receptacles. "Circuit
Breaker" built into box for convenient reset. The GFCI is an
integral part of the male connector. Provides protection to
the entire cord as well as tools attached. Built to withstand
outdoor - rugged type construction. Applications include:
|
|
- Lighting
- Multiple tools
- Construction Sites
|
Standard lengths: 2', 6', 25', 50' and 99'. To prevent
unmonitored equipment startup, manual reset is required after GFCI
trip and power outage. Complies with National Electric Code
(NEC 2008) Article 590.6 for "Temporary Installations".
GFCI Protected Right Angle Plug Quad Boxes Product Sheet
| Part Number | Features | Config | Listed |
|---|
14880-R2F-402-BI (2’)
14880-003 (6’)
14880-425-BI (25’)
14880-450-BI (50’)
14880-121 (99’)
| - Volts/Amps: 120V/15A
- Cord Gauge: 12/3 AWG.
- NEMA 5-15P & (4)5-15R Outlets
- Trip Level: 4-6 mA
- 15A breaker
|  |   |
| Grounded neutral | 4 Ohms typical
|
| Trip response time for ground fault and grounded neutral trip | less than 25mS
|
| Voltage surge withstand | 3kv ringwave test and 4kv/2kA surge immunity test
|
| Radio frequency noise susceptibility | operates within normal limits with 0.5 volts injected on power line 150kHz-230mHz
|
| Frequency | 50/60 Hz
|
| Endurance | 3,000 operations minimum
|
| Overload current | six times rated current
|
| Operating temperature range | -35˚C to 66˚C
|
| Effect of 10 Amp turn DC Shock on ground fault trip | 5% maximum trip level variation
|
| Insulation voltage | 1500 VRMS - 1a Min.
|
| Power on indication | mechanical indicator |