GFCI In-Line User Attachables
120V/20A & 240V/20A
12-18 AWG.
The in-line user attachable is ideal for existing equipment
without GFCI protection, and can be easily attached by connecting
the GFCI in series with the supply cable 9 to 10 inches from the
plug end to provide GFCI protection. Applications
include:
- Pressure Washers
- Drain Snakes
- Floor Cleaners
- Industrial Appliances
|
- Power Tool
- Pumps
- Boat Lifts
- Extension Cords
|
Rainproof rated, UL listed for outdoor use. To prevent
unmonitored equipment startup, manual reset is required after GFCI
trip and power outage. Allows compliance with National
Electric Code (NEC 2008) Article 590.6 for "Temporary
Installations" and OSHA regulation. Available with yellow or
black case.
GFCI In-Line User Attachables Product Sheet
| Part Number | Features | Config | Listed |
|---|
25000-016 GFCI
| - Volts/Amps: 120V/20A & 240V/20A
- Accepts 12-18 AWG.(SJT)
- Trip Level: 4-6 mA
| |   |
25230-001 GFCI
| - Volts/Amps: 120V/20A
- Accepts 12-18 AWG.(SJT)
- Trip Level: 4-6 mA
| |   |
| Grounded neutral | 4 Ohms typical
|
| Trip response time for ground fault and grounded neutral trip | less than 25mS
|
| Voltage surge withstand | 3kv ringwave test and 4kv/2kA surge immunity test
|
| Radio frequency noise susceptibility | operates within normal limits with 0.5 volts injected on power line 150kHz-230mHz
|
| Frequency | 50/60 Hz
|
| Endurance | 3,000 operations minimum
|
| Overload current | six times rated current
|
| Operating temperature range | -35˚C to 66˚C
|
| Effect of 10 Amp turn DC Shock on ground fault trip | 5% maximum trip level variation
|
| Insulation voltage | 1500 VRMS - 1 Min.
|
| Power on indication | lighted indicator |