ELCI In-Line User Attachables
120V/20A, 240V/16A & 240V/20A
Dual user attachable configuration for OEM connection of cable.
Units are dual voltage rated. Operation and trip times
equal or exceed that of the GFCI's. Provides equipment
protection for office equipment. Applications include:
- Copiers
- Printers
- Scanners
|
- Film Processors
- Image Setters
- Appliances
|
To prevent unmonitored equipment startup, manual reset is
required after ELCI trip. Does not require reset following
disruption of primary power. Available with black case
only.
ELCI In-Line User Attachables Product Sheet
| Trip response time for ground fault | less than 25mS
|
| Voltage surge withstand | 3kv ringwave test and 4kv/2kA surge immunity test
|
| Radio frequency noise susceptibility | operates within normal limits with 0.5 volts injected on power line 150kHz-230mHz
|
| Frequency | 50 / 60 Hz
|
| Endurance | 5,000 operations minimum
|
| Overload current | six times rated current
|
| Operating temperature range | +10˚C to +60˚C
|
| Effect of 10 Amp turn DC Shock on ground fault trip | 5% maximum trip level variation
|
| Insulation voltage | 1500 VRMS - 1 Min.
|
| Power on indication | lighted indicator |